SW190 Technical Information
|
Application |
Interrupted Uninterrupted |
|
|
Thermal Current Rating |
150A |
200A |
|
Intermittent Current Rating: |
||
|
30% Duty |
275A |
365A |
|
40% Duty |
235A |
315A |
|
50% Duty |
210A |
285A |
|
60% Duty |
195A |
260A |
|
70% Duty |
180A |
240A |
|
Rated Fault Current Breaking Capacity (Icn) 5ms Time Constant:(In accordance with UL583*) |
||
|
Blowouts |
600A at 120V D.C. |
|
|
No Blowouts |
1000A at 80V D.C. |
|
|
Rated Fault Current Breaking Capacity (Icn) Resistive Load:(In accordance with UL508*) |
||
|
Blowouts |
300A at 120V D.C. |
|
|
No Blowouts |
300A at 60V D.C. |
|
|
Maximum Recommended Contact Voltages |
||
|
Blowouts |
250V |
250V |
|
No Blowouts |
96V |
96V |
|
Typical Voltage Drop per pole across New Contacts at 150A |
40mV |
|
|
|
||
|
Mechanical Durability |
> 5,000,000 Cycles |
|
|
Coil Voltage Available (Us) (Rectifier board required for A.C.) |
6 - 240V |
|